STATE OF INDIANA

)

SS:

BEFORE THE INDIANA DEPARTMENT OF

 

)

 

 

COUNTY OF MARION

)

 

ENVIRONMENTAL MANAGEMENT

 

COMMISSIONER OF THE DEPARTMENT

)

 

OF ENVIRONMENTAL MANAGEMENT,

 

)

 

 

 

)

 

Complainant,

 

)

 

 

 

)

 

 

v.

 

)

Case No. 2021-27886-U

 

 

)

 

TRUEBLOOD OIL CORPORATION,

 

)

 

PARAMJIT SINGH, JASPAL KAUR,

 

)

 

 

 

)

 

Respondents.

 

)

 

 

AGREED ORDER

 

Complainant and Respondents desire to settle and compromise this action without hearing or adjudication of any issue of fact or law, and consent to the entry of the following Findings of Fact and Order. Pursuant to Indiana Code (“IC”) 13-30-3-3, entry into the terms of this Agreed Order does not constitute an admission of any violation contained herein. Respondents’ entry into this Agreed Order shall not constitute a waiver of any defense, legal or equitable, which Respondents may have in any future administrative or judicial proceeding, except a proceeding to enforce this order.

 

I.  FINDINGS OF FACT

 

1.            Complainant is the Commissioner (“Complainant”) of the Indiana Department of Environmental Management (“IDEM”), a department of the State of Indiana created by Indiana Code (“IC”) 13-13-1-1.

 

2.            Respondent, Trueblood Oil Corporation (“Respondent), owns and operates the facility with Facility ID No. 2932, located at 3409 North High School Road, in Indianapolis, Marion County, Indiana (“Site”).

 

3.            Respondents, Paramjit Singh and Jaspal Kaur, own Parcel #49-05-24-151-017.000-901 located at 3409 North High School Road, Indianapolis, Marion County, Indiana (the “Site”). The UST systems are installed at the Site.

 

4.            Respondent, Trueblood Oil Corporation, owns and operates two 12,000-gallon steel USTs installed in July 1990. The piping is single walled fiberglass.

 

5.            IDEM has jurisdiction over the parties and the subject matter of this action.

 

6.            Pursuant to IC 13-30-3-3, IDEM issued a Notice of Violation (“NOV”) on August 11, 2021, via Certified Mail to:

 

Paramjit Singh, President and Registered Agent for

Trueblood Oil Corporation

12913 Broncos Drive

Fishers, Indiana 46037

 

Paramjit Singh and Jaspal Kaur, Property Owners

3409 North High School Road

Indianapolis, Indiana 46224

 

7.            During an investigation including an inspection on October 8, 2020, conducted by a representative of IDEM, the following violations were found:

 

a.         Pursuant to 329 Indiana Administrative Code (“IAC”) 9-2-2(a), all notifications required to be submitted under this article must be submitted on a form provided by the department and in a format prescribed by the commissioner.

 

As noted during the inspection, the premium fill port was observed to not be equipped with an auto shut off device. A rectifier box was not present and other corrosion protection records were not available on-site. The facility representative also stated there was no ATG on-site, and the inspector did not observe one. Previous notification forms have listed auto shut off as the overfill prevention equipment installed and ATG as the form of release detection.

 

An updated notification form was submitted on April 10, 2015; however, deficiencies were noted, and a Notice of Deficiency (NOD) issued June 3, 2015.

 

A notification form was submitted on October 25, 2021, was submitted. Deficiencies were noted and a NOD issued November 8, 2021. A corrected form has not been received to date.

 

b.         Pursuant to 40 Code of Federal Regulations (“CFR”) 280.34, owners and operators of UST systems must cooperate fully with inspections, monitoring and testing conducted by the implementing agency, as well as requests for document submission, testing, and monitoring by the owner or operator pursuant to section 9005 of Subtitle I of the Solid Waste Disposal Act, as amended.

 

As noted during the inspection, a records request was issued January 8, 2020. No response was provided, and the facility representative stated no records were available on-site.

 

c.         Pursuant to 329 IAC 9-8-11(b), an owner or operator of:

(1)       twelve (12) or fewer USTs shall demonstrate the ability to pay the applicable deductible amount under IC 13-23-9-1.3; or

(2)       more than twelve (12) USTs shall demonstrate the ability to pay two (2) times the applicable deductible amount under IC 13-23-9-1.3.

 

As noted during the inspection, a mechanism of financial responsibility was not provided.

 

On December 6 and 21, 2021, Respondent submitted a letter of credit; however, it did not contain information required by statute.

 

d.         Pursuant to 40 CFR 280.21(d), to prevent spilling and overfilling associated with product transfer to the UST system, all existing UST systems must comply with UST system spill and overfill prevention equipment requirements specified in § 280.20(c).

 

As noted during the inspection, the regular spill bucket was not installed to standard, and the premium fill port was not observed to have an auto shut off device installed.

 

Documentation submitted showing the regular spill bucket was replaced in September 2021, and coaxial drop tubes installed on both tanks in October 2021.

 

e.         Pursuant to 40 CFR 280.31(a), all corrosion protection systems must be operated and maintained to continuously provide corrosion protection to the metal components of that portion of the tank and piping that routinely contain regulated substances and are in contact with the ground.

 

As noted during the inspection, the facility representative stated that no corrosion protection testing records were available on-site.

 

Documentation of corrosion protection testing dated March 1, 2021, was submitted.

 

f.          Pursuant to 40 CFR 280.31(b), all UST systems equipped with cathodic protection systems must be inspected for proper operation by a qualified cathodic protection tester in accordance with the following requirements:

(1)       Frequency. All cathodic protection systems must be tested within 6 months of installation and at least every 3 years thereafter or according to another reasonable time frame established by the implementing agency; and

(2)       Inspection criteria. The criteria that are used to determine that cathodic protection is adequate as required by this section must be in accordance with a code of practice developed by a nationally recognized association.

 

As noted during the inspection, Respondents failed to have the cathodic protection systems tested by a qualified cathodic protection tester as required.

 

Respondents submitted documentation of cathodic testing results dated March 1, 2021.

 

g.         Pursuant to 40 CFR 280.40(a)(1), owners and operators of UST systems must provide a method, or combination of methods, of release detection that can detect a release from any portion of the tank and the connected underground piping that routinely contains product.

 

As noted during the inspection, the inspector was unable to gain access to the room where the ATG was kept, and release detection records for the USTs and piping was not available.

 

Respondents submitted documentation of installation of a new ATG, and functionality test dated March 1, 2021.

 

h.         Pursuant to 40 CFR 280.41(b)(1)(i)(A), considering previous Indiana rules at 329 IAC 9-2-1(2)(D) and 329 IAC 9-3-1.3  (both repealed 2018), pressurized underground piping installed on or before September 2, 2009 that routinely contains regulated substances must be equipped with an automatic line leak detector conducted in accordance with § 280.44(a); and have an annual line tightness test conducted in accordance with § 280.44(b) or have monthly monitoring conducted in accordance with § 280.44(c).

 

As noted during the inspection, the annual leak detector test was not provided.

 

Respondents submitted documentation of leak detector testing dated March 1, 2021.

 

7.         Orders of the Commissioner are subject to administrative review by the Office of Environmental Adjudication under IC 4-21.5; however, in recognition of the settlement reached, Respondents acknowledge notice of this right and waive any right to administrative and judicial review of this Agreed Order.

 

II.  ORDER

 

1.            This Agreed Order shall be effective (“Effective Date”) when it is approved by Complainant or Complainant’s delegate and has been received by Respondents. This Agreed Order shall have no force or effect until the Effective Date.

 

2.            Respondents shall comply with the rules listed in the findings of fact above.

 

3.            Immediately upon the Effective Date, Respondents shall comply with 40 CFR 280.34. Specifically, Respondent shall cooperate fully with inspections, monitoring and testing conducted by the implementing agency, as well as requests for document submission, testing, and monitoring by the owner or operator pursuant to section 9005 of Subtitle I of the Solid Waste Disposal Act, as amended to IDEM.

 

4.            Within thirty (30) days of the Effective Date, Respondents shall comply with 329 IAC 9-2-2(a). Specifically, Respondents shall download and submit the “Notification Form for Underground Storage Tanks,” State Form 45223 from IDEM webpage: https://www.in.gov/idem/5157.htm, under “Underground Storage Tank (UST) Program” indicating the correct overfill protection equipment installed, release detection method, and corrosion protection method for the UST systems. Once downloaded the form may be completed on-line or by hand and emailed to USTRegistration@idem.in.gov. The completed form will not be accepted by mail.

 

5.            Within thirty (30) days of the Effective Date, Respondents shall comply with 329 IAC 9-8-11(b). Specifically, Respondents shall submit a copy of the instrument proving they have the coverage required by this rule.

 

6.            All submittals required by this Agreed Order, unless Respondents are notified otherwise in writing by IDEM, shall be sent to:

 

Jodi Pisula, Enforcement Case Manager

Office of Land Quality

Indiana Department of Environmental Management

100 North Senate Avenue

Indianapolis, IN 46204-2251

 

7.            Respondents are assessed and agree to pay a civil penalty of Fifteen Thousand Eight Hundred Forty Dollars ($15,840.00). Said penalty amount shall be due and payable to the Underground Petroleum Storage Tank Trust Fund in twelve (12) monthly installments.  The first installment of One Thousand Three Hundred Twenty Dollars ($1,320.00) shall be paid within thirty (30) days of the Effective Date; the 30th day being the “Due Date”, and the remaining installment payments shall be made every thirty (30) days thereafter. Interest shall be accrued on unpaid amounts at the rate established by IC 24-4.6-1-101.

 

8.            In the event the terms and conditions of the following paragraphs are violated, Complainant may assess, and Respondents shall pay a stipulated penalty in the following amount:

 

Paragraph

Penalty

Order paragraph #4

$100.00 per week late

Order paragraph #5

$100.00 per week late

 

9.            Stipulated penalties shall be due and payable no later than the 30th day after Respondents receive written notice that Complainant has determined a stipulated penalty is due; the 30th day being the “Due Date.” Complainant may notify Respondents at any time that a stipulated penalty is due. Failure to notify Respondents in writing in a timely manner of stipulated penalty assessment shall not waive Complainant’s right to collect such stipulated penalty or preclude Complainant from seeking additional relief against Respondents for violation of this Agreed Order. Neither assessment nor payment of stipulated penalties shall preclude Complainant from seeking additional relief against Respondents for a violation of this Agreed Order; such additional relief includes any remedies or sanctions available pursuant to Indiana law, including, but not limited to, civil penalties pursuant to IC 13-30-4.

 

10.         Civil and stipulated penalties are payable by check to the “Underground Petroleum Storage Tank Trust Fund.” Checks shall include the Case Number of this action and shall be mailed to:

 

Indiana Department of Environmental Management

Accounts Receivable

IGCN, Room 1340

100 North Senate Avenue

 

11.         In the event that the monies due to IDEM pursuant to this Agreed Order are not paid on or before their Due Date, Respondents shall pay interest on the unpaid balance at the rate established by IC 24-4.6-1. The interest shall be computed as having accrued from the Due Date until the date that Respondents pay any unpaid balance. Such interest shall be payable to the Underground Petroleum Storage Tank Trust Fund and shall be payable to IDEM in the manner specified in Paragraph 10, above.

 

12.         Signatories to this Agreed Order certify that they are fully authorized to execute this Agreed Order and legally bind the party they represent.

 

13.         This Agreed Order shall jointly and severally apply to and be binding upon Respondents and all successors and assigns. Respondents shall provide a copy of this Agreed Order, if in force, to any subsequent owners, successors, or assigns before ownership rights are transferred.

 

14.         No change in ownership, corporate, or partnership status of Respondents shall in any way alter the Respondents’ status or responsibilities under this Agreed Order.

 

15.         Respondents shall ensure that all contractors, firms, and other persons performing work under this Agreed Order comply with the terms of this Agreed Order.

 

16.         In the event that any terms of this Agreed Order are found to be invalid, the remaining terms shall remain in full force and effect and shall be construed and enforced as if this Agreed Order did not contain the invalid terms.

 

17.         This Agreed Order is not and shall not be interpreted to be a permit or a modification of an existing permit. This Agreed Order, and IDEM’s review or approval of any submittal made by Respondents pursuant to this Agreed Order, shall not in any way relieve Respondents of the obligation to comply with the requirements of any applicable permits or any applicable Federal or State laws or regulations.

 

18.         Complainant does not, by its approval of this Agreed Order, warrant or aver in any manner that Respondents’ compliance with any aspect of this Agreed Order will result in compliance with the provisions of any permit, order, or any applicable Federal or State law or regulation. Additionally, IDEM or anyone acting on its behalf shall not be held liable for any costs or penalties Respondents may incur as a result of Respondents’ efforts to comply with this Agreed Order.

 

19.         Nothing in this Agreed Order shall prevent or limit IDEM’s rights to obtain penalties or injunctive relief under any applicable Federal or State law or regulation, except that IDEM may not, and hereby waives its right to seek additional civil penalties for the violations specified in the NOV.

 

20.         Nothing in this Agreed Order shall prevent IDEM or anyone acting on its behalf from communicating with the U.S. Environmental Protection Agency (U.S. EPA) or any other agency or entity about any matters relating to this enforcement action. IDEM or anyone acting on its behalf shall not be held liable for any costs or penalties Respondents may incur as a result of such communications with the U.S. EPA or any other agency or entity.

 

21.         This Agreed Order shall remain in effect until IDEM issues a Resolution of Case letter to Respondents.

 

TECHNICAL RECOMMENDATION:

RESPONDENT:

Department of Environmental Management

Trueblood Oil Corporation

 

 

By: _______________________

By:_________________________

Jennifer Reno, Section Chief

Land Enforcement Section

Printed: ______________________

Office of Land Quality

Title: ________________________

Date: ___________

Date: _______________________

COUNSEL FOR RESPONDENT:

By: ________________________

Date: ______________________

APPROVED AND ADOPTED BY THE INDIANA DEPARTMENT OF ENVIRONMENTAL

MANAGEMENT THIS

_________

DAY OF

________________________,

20__.

For the Commissioner:

Signed 1/28/2022

Peggy Dorsey, Assistant Commissioner

Office of Land Quality