-IR- Database Guide
-IR- Database: Indiana Register

TITLE 675 FIRE PREVENTION AND BUILDING SAFETY COMMISSION

Proposed Rule
LSA Document #11-84

DIGEST

Adds 675 IAC 14-4.3-139.1 to amend the energy conservation provisions. Repeals 675 IAC 14-4.3-139. Effective 30 days after filing with the Publisher.



SECTION 1. 675 IAC 14-4.3-139.1 IS ADDED TO READ AS FOLLOWS:

Rule 4.3. 2005 Indiana Residential Code


675 IAC 14-4.3-139.1 Chapter 11; energy efficiency

Authority: IC 22-13-2
Affected: IC 22-13


Sec. 139.1. Delete the text of Chapter 11 in its entirety and substitute the following modified text from Chapter 11 of the 2009 International Residential Code, published by the International Code Council, Inc., 4051 West Flossmoor Road, Country Club Hills, IL 60478-5795:
SECTION N1101; GENERAL N1101.1 Scope.
This chapter regulates the energy efficiency for the design and construction of buildings regulated by this code.
Exception: Portions of the building envelope that do not enclose conditioned space are exempt from building thermal envelope provisions of this chapter.
N1101.2 Compliance. Compliance shall be demonstrated by meeting the requirements of this chapter. Climate zones from Figure N1101.2 or Table N1101.2 shall be used in determining the applicable requirements from this chapter.
675110084PRA011.jpg
TABLE N1101.2 
CLIMATE ZONES AND MOISTURE REGIMES OF INDIANA COUNTIES 
Key: A – Moist 
5A Adams  5A Elkhart  4A Jennings  4A Orange  4A Switzerland 
5A Allen  5A Fayette  5A Johnson  5A Owen  5A Tippecanoe 
5A Bartholomew  4A Floyd  4A Knox  5A Parke  5A Tipton 
5A Benton  5A Fountain  5A Kosciusko  4A Perry  5A Union 
5A Blackford  5A Franklin  5A LaGrange  4A Pike  4A Vanderburgh 
5A Boone  5A Fulton  5A Lake  5A Porter  5A Vermillion 
4A Brown  4A Gibson  5A LaPorte  4A Posey  5A Vigo 
5A Carroll  5A Grant  4A Lawrence  5A Pulaski  5A Wabash 
5A Cass  4A Greene  5A Madison  5A Putnam  5A Warren 
4A Clark  5A Hamilton  5A Marion  5A Randolph  4A Warrick 
5A Clay  5A Hancock  5A Marshall  4A Ripley  4A Washington 
5A Clinton  5A Hendricks  4A Martin  5A Rush  5A Wayne 
4A Crawford  5A Henry  5A Miami  4A Scott  5A Wells 
4A Daviess  5A Howard  4A Monroe  5A Shelby  5A White 
4A Dearborn  5A Huntington  5A Montgomery  4A Spencer  5A Whitley 
5A Decatur  4A Jackson  5A Morgan  5A Starke   
5A Dekalb  5A Jasper  5A Newton  5A Steuben   
5A Delaware  5A Jay  5A Noble  5A St. Joseph   
4A Dubois  4A Jefferson  4A Ohio  4A Sullivan   
N1101.3 Identification. Materials, systems and equipment shall be identified in a manner that will allow a determination of compliance with the applicable provisions of this chapter.
N1101.4 Building thermal envelope insulation. An R-value identification mark shall be applied by the manufacturer to each piece of building thermal envelope insulation 12 inches (305 mm) or more wide. Alternately, the insulation installers shall provide a certification listing the type, manufacturer and R-value of insulation installed in each element of the building thermal envelope. For blown or sprayed insulation (fiberglass and cellulose), the initial installed thickness, settled thickness, settled R-value, installed density, coverage area and number of bags installed shall be listed on the certification. For sprayed polyurethane foam (SPF) insulation, the installed thickness of the area covered and R-value of installed thickness shall be listed on the certificate. The insulation installer shall sign, date and post the certificate in a conspicuous location on the job site.
N1101.4.1 Blown or sprayed roof/ceiling insulation. The thickness of blown in or sprayed roof/ceiling insulation (fiberglass or cellulose) shall be written in inches (mm) on markers that are installed at least one for every 300 ft2 (28m2) throughout the attic space. The markers shall be affixed to the trusses or joists and marked with the minimum initial installed thickness with numbers a minimum of 1 inch (25 mm) high. Each marker shall face the attic access opening. Spray polyurethane foam thickness and installed R-value shall be listed on the certificate provided by the insulation installer.
N1101.4.2 Insulation mark installation. Insulating materials shall be installed such that the manufacturer's R-value mark is readily observable upon inspection.
N1101.5 Fenestration product rating. U-factors of fenestration products (windows, doors and skylights) shall be determined in accordance with NFRC 100 by an accredited, independent laboratory, and labeled and certified by the manufacturer. Products lacking such a labeled U-factor shall be assigned a default U-factor from Tables N1101.5(1) and N1101.5(2).
TABLE N1101.5(1) 
DEFAULT GLAZED FENESTRATION U-FACTORS 
FRAME TYPE  SINGLE PANE  DOUBLE PANE  SKYLIGHT 
Single  Double 
Metal  1.2  0.8  2  1.3 
Metal with thermal break  1.1  0.65  1.9  1.1 
Nonmetal or metal clad  0.95  0.55  1.75  1.05 
Glazed block  0.6 
TABLE N1101.5(2) 
DEFAULT DOOR U-FACTORS 
DOOR TYPE  U-FACTOR 
Uninsulated metal  1.2 
Insulated metal  0.6 
Wood  0.5 
Insulated, nonmetal edge, max 45% glazing, any glazing double pane  0.35 
N1101.6 Insulation product rating. The thermal resistance (R-value) of insulation shall be determined in accordance with the 16 CFR 460 as in effect on March 1, 2011, in units of h • ft2 • °F/Btu at a mean temperature of 75°F (24°C).
N1101.7 Installation. All materials, systems and equipment shall be installed in accordance with the manufacturer's installation instructions and the provisions of this chapter.
N1101.7.1 Protection of exposed foundation insulation. Insulation applied to the exterior of basement walls, crawl space walls and the perimeter of slab-on-grade floors shall have a rigid, opaque and weather-resistant protective covering to prevent the degradation of the insulation's thermal performance. The protective covering shall cover the exposed exterior insulation and extend a minimum of six (6) inches (152 mm) below grade.
N1101.8 Certificate. A permanent certificate shall be posted on or in the electrical distribution panel. The certificate shall not cover or obstruct the visibility of the circuit directory label, service disconnect label or other required labels. The certificate shall be completed by the builder or registered design professional. The certificate shall list the predominant R-values of insulation installed in or on ceiling/roof, walls, foundation (slab, basement wall, crawl space wall and/or floor), ducts outside conditioned spaces, and U-factors for fenestration. Where there is more than one value for each component, the certificate shall list the value covering the largest area. The certificate shall list the types and efficiencies of heating, cooling and service water heating equipment. Where a gas-fired unvented room heater, electric furnace, and/or baseboard electric heater is installed in the residence, the certificate shall list "gas-fired unvented room heater", "electric furnace", or "baseboard electric heater" as appropriate. An efficiency shall not be listed for gas-fired unvented room heaters, electric furnaces, or electric baseboard heaters.
SECTION N1102; BUILDING THERMAL ENVELOPE
N1102.1 Insulation and fenestration criteria. The building thermal envelope shall meet the requirements of Table N1102.1 based on the climate zone specified in Table N1101.2.
N1102.1.1 R-value computation. Insulation material used in layers, such as framing cavity insulation and insulating sheathing, shall be summed to compute the component R-value. The manufacturer's settled R-value shall be used for blown insulation. Computed R-values shall not include an R-value for other building materials or air films.
N1102.1.2 U-factor alternative. An assembly with a U-factor equal to or less than that specified in Table N1102.1.2 shall be permitted as an alternative to the R-value in Table N1102.1.
N1102.1.3 Total UA alternative. If the total building thermal envelope UA (sum of U-factor times assembly area) is less than or equal to the total UA resulting from using the U-factors in Table N1102.1.2 (multiplied by the same assembly area as in the proposed building), the building shall be considered in compliance with Table N1102.1. The UA calculation shall be done using a method consistent with the Indiana Energy Conservation Code, 675 IAC 19-4, and shall include the thermal bridging effects of framing materials. Calculation procedures used to comply with this section shall be by use of computer software tools capable of calculating the total building thermal envelope UA that differs between "standard reference design" and the proposed design. REScheck, from the US Department of Energy, is an example of an approved software tool.
TABLE N1102.1 
INSULATION AND FENESTRATION REQUIREMENTS BY COMPONENT a 
CLIMATE ZONE  FENESTRATION U-FACTOR  SKYLIGHT U-FACTORb  CEILING R-VALUE  WOOD FRAME R-VALUE  MASS WALL R-VALUE g  FLOOR R-VALUE  BASEMENT WALL R-VALUE c  SLAB R-VALUE AND DEPTH d  CRAWL SPACE R-VALUE 
4  0.35  0.60  38  13  5/10  19  10/13  10; 2 ft  10/13 
5  0.35  0.60  38  20 or 13 + 5f  13/17  30 e  10/13  10; 2 ft  10/13 
a. R-values are minimums. U-factors are maximums. R-19 batts compressed in to a nominal 2 × 6 framing cavity such that the R-value is reduced by R-1 or more shall be marked with the compressed batt R-value in addition to the full thickness R-value. 
b. The fenestration U-factor column excludes skylights. 
c. The first R-value applies to continuous insulation, the second to framing cavity insulation; either insulation meets the requirement. 
d. R-5 shall be added to the required slab edge R-values for heated slabs. 
e. Or insulation sufficient to fill the framing cavity, R-19 minimum. 
f. "13+5" means R-13 cavity insulation plus R-5 insulated sheathing. If structural sheathing covers 25% or less of the exterior, R-5 sheathing is not required where structural sheathing is used. If structural sheathing covers more than 25% of exterior, structural sheathing shall be supplemented with insulated sheathing of at least R-2. 
g. The second R-value applies when more than half the insulation is on the interior. 
TABLE N1102.1.2 
EQUIVALENT U-FACTORS a 
CLIMATE ZONE  FENESTRATION U-FACTOR  SKYLIGHT U-FACTOR  CEILING U-FACTOR  FRAME WALL U-FACTOR  MASS WALL U-FACTOR b  FLOOR U-FACTOR  BASEMENT WALL U-FACTOR  CRAWL SPACE WALL U-FACTOR 
4  0.35  0.60  0.030  0.082  0.141  0.047  0.059  0.065 
5  0.35  0.60  0.030  0.057  0.082  0.033  0.059  0.065 
a. Nonfenestration U-factors shall be obtained from measurement, calculation or an approved source. 
b. When more than half the insulation is on the interior, the mass wall U-factors shall be a maximum of 0.10 in zone 4 and the same as the frame wall U-factor (0.057) in zone 5. 
N1102.2 Specific insulation requirements.
N1102.2.1 Ceilings with attic spaces. When Section N1102.1 would require R-38 in the ceiling, R-30 shall be deemed to satisfy the requirement for R-38 wherever the full height of uncompressed R-30 insulation extends over the wall top plate at the eaves. Similarly R-38 shall be deemed to satisfy the requirement for R-49 wherever the full height of uncompressed R-38 insulation extends over the wall top plate at the eaves. This reduction shall not apply to the U-factor alternative approach in Section N1102.1.2 and the Total UA alternative in Section N1102.1.3.
N1102.2.2 Ceilings without attic spaces. Where Section N1102.1 would require insulation levels above R-30 and the design of the roof/ceiling assembly does not allow sufficient space for the required insulation, the minimum required insulation for such roof/ceiling assemblies shall be R-30. This reduction of insulation from the requirements of N1102.1 shall be limited to five hundred (500) square feet (46 m2) or twenty (20) percent of the total insulated ceiling area, whichever is less. This reduction shall not apply to the U-factor alternative approach in Section N1102.1.2 and the Total UA alternative in Section N1102.1.3.
N1102.2.3 Access hatches and doors. Access hatches from conditioned spaces to unconditioned spaces (e.g., attics and crawl spaces) shall be weatherstripped and insulated to a level equivalent to the insulation on the surrounding surfaces. Access shall be provided to all equipment which prevents damaging or compressing the insulation. A wood framed or equivalent baffle or retainer is required to be provided when loose fill insulation is installed, the purpose of which is to prevent the loose fill insulation from spilling into the living space when the attic access is opened and to provide a permanent means of maintaining the installed R-value of the loose fill insulation.
N1102.2.4 Mass walls. Mass walls, for the purposes of this chapter, shall be considered above-grade walls of concrete block, concrete, insulated concrete form (ICF), masonry cavity, brick (other than brick veneer), earth (adobe, compressed earth block, rammed earth) and solid timber/logs.
N1102.2.5 Steel-frame ceilings, walls and floors. Steel frame ceilings, walls and floors shall meet the insulation requirements of Table N1102.2.5 or shall meet the U-factor requirements in Table N1102.1.2. The calculation of the U-factor for a steel-frame envelope assembly shall use a series-parallel path calculation method.
TABLE N1102.2.5 
STEEL-FRAME CEILING, WALL AND FLOOR INSULATION ( R-VALUE) 
WOOD FRAME R-VALUE REQUIREMENT  COLD-FORMED STEEL EQUIVALENT R-VALUE a 
Steel Truss Ceilings a 
R-30  R-38 or R-30 + 3 or R-26 + 5 
R-38  R-49 or R-38 + 3 
R-49  R-38 + 5 
Steel Joist Ceilings b 
R-30  R-38 in 2 × 4 or 2 x 6 or 2 × 8; R-49 in any framing 
R-38  R-49 in 2 × 4 or 2 × 6 or 2 × 8 or 2 × 10 
Steel Framed Wall 
R-13  R-13 + 5 or R-15 + 4 or R-21 + 3 or R-0 + 10 
R-19  R-13 + 9 or R-19 + 8 or R-25 + 7 
R-21  R-13 +10 or R-19 + 9 or R-25 + 8 
Steel Joist Floor 
R-13  R-19 in 2 × 6 or R-19 + R-6 in 2 × 8 or 2 × 10 
R-19  R-19 + R-6 in 2 × 6 or R-19 + R-12 in 2 × 8 or 2 × 10 
For SI: 1 inch = 25.4 mm. 
a. Cavity insulation R-value is listed first, followed by continuous insulation R-value. 
b. Insulation exceeding the height of the framing shall cover the framing. 
N1102.2.6 Floors. Floor insulation shall be installed to maintain permanent contact with the underside of the subfloor decking.
N1102.2.7 Basement walls. Exterior walls associated with conditioned basements shall be insulated from the top of the basement wall down to ten (10) feet (3048 mm) below grade or to the basement floor, whichever is less. Walls associated with unconditioned basements shall meet this requirement unless the floor overhead is insulated in accordance with Sections N1102.1 and N1102.2.5.
N1102.2.8 Slab-on-grade floors. Slab-on-grade floors with a floor surface less than twelve (12) inches below grade shall be insulated in accordance with Table N1102.1. The insulation shall extend downward from the top of the slab on the outside or inside of the foundation wall. Insulation located below grade shall be extended the distance provided in Table N1102.1 by any combination of vertical insulation, insulation extending under the slab or insulation extending out from the building. Insulation extending away from the building shall be protected by pavement or by a minimum of ten (10) inches (254 mm) of soil. The top edge of the insulation installed between the exterior wall and the edge of the interior slab shall be permitted to be cut at a 45-degree (0.79 rad) angle away from the exterior wall.
N1102.2.9 Crawl space walls. As an alternative to insulating floors over crawl spaces, crawl space walls shall be permitted to be insulated when the crawl space is not vented to the outside. Crawl space wall insulation shall be permanently fastened to the wall and extend downward from the floor to the finished grade level and then vertically and/or horizontally for at least an additional twenty-four (24) inches (610 mm). Exposed earth in unvented crawl space foundations shall be covered with a continuous 0.1 perms or less vapor retarder. All joints of the vapor retarder shall overlap by six (6) inches (153 mm) and be sealed or taped. The edges of the vapor retarder shall extend at least six (6) inches (153 mm) up the stem wall and shall be attached to the stem wall.
N1102.2.10 Masonry veneer. Insulation shall not be required on the horizontal portion of the foundation that supports a masonry veneer.
N1102.2.11 Thermally isolated sunroom insulation. The minimum ceiling insulation R-values shall be R-19 in zone 4 and R-24 in zone 5. The minimum wall R-value shall be R-13 in all zones. New wall(s) separating the sunroom from conditioned space shall meet the building thermal envelope requirements.
N1102.3 Fenestration.
N1102.3.1 U-factor. An area-weighted average of fenestration products shall be permitted to satisfy the U-factor requirements.
N1102.3.2 Glazed fenestration exemption. Up to fifteen (15) square feet (1.4m2) of glazed fenestration per dwelling unit shall be permitted to be exempt from U-factor in Section N1102.1. This exemption shall not apply to the U-factor alternative approach in Section N1102.1.2 and the Total UA alternative in Section N1102.1.3.
N1102.3.3 Opaque door exemption. One side-hinged opaque door assembly up to twenty-four (24) square feet (2.22 m2) in area is exempted from the U-factor requirement in Section N1102.1. This exemption shall not apply to the U-factor alternative approach in Section N1102.1.2 and the Total UA alternative in Section N1102.1.3.
N1102.3.4 Thermally isolated sunroom U-factor. For zones 4 and 5, the maximum fenestration U-factor shall be 0.50 and the maximum skylight U-factor shall be 0.75. New windows and doors separating the sunroom from conditioned space shall meet the building thermal envelope requirements.
N1102.3.5 Replacement fenestration. Where some or all of an existing fenestration unit is replaced with a new fenestration product, including sash and glazing, the replacement fenestration unit shall meet the applicable requirements for U-factor in Table N1102.1.
N1102.4 Air leakage.
N1102.4.1 Building thermal envelope. The building thermal envelope shall be durably sealed to limit infiltration. The sealing methods between dissimilar materials shall allow for differential expansion and contraction. The following shall be caulked, gasketed, weatherstripped or otherwise sealed with an air barrier material, suitable film or solid material.
1. All joints, seams and penetrations.
2. Site-built windows, doors and skylights.
3. Openings between window and door assemblies and their respective jambs and framing.
4. Utility penetrations.
5. Dropped ceilings or chases adjacent to the thermal envelope.
6. Knee walls.
7. Walls and ceilings separating the garage from conditioned spaces.
8. Behind tubs and showers on exterior walls.
9. Common walls between dwelling units.
10. Attic access openings.
11. Rim joists junction.
12. Other sources of infiltration.
N1102.4.2 Air sealing and insulation. Building envelope, air tightness and insulation installation shall be demonstrated to comply with one of the following options given by Section N1102.4.2.1 or N1102.4.2.2.
TABLE N1102.4.2 
AIR BARRIER AND INSULATION INSPECTION 
COMPONENT  CRITERIA 
Air barrier and thermal barrier  Exterior thermal envelope insulation for framed walls is installed in substantial contact and continuous alignment with building envelope air barrier. Breaks or joints in the air barrier are filled or repaired. Air-permeable insulation is not used as a sealing material. Air-permeable insulation is inside of an air barrier. 
Ceiling/attic  Air barrier in any dropped ceiling/soffit is substantially aligned with insulation and any gaps are sealed. Attic access (except unvented attic), knee wall door, or drop down stair is sealed. 
Walls  Corners and headers are insulated. Junction of foundation and sill plate is sealed. 
Windows and doors  Space between window/door jambs and framing is sealed. 
Rim joists  Rim joists are insulated and include an air barrier. 
Floors (including above garage and cantilevered floors)  Insulation is installed to maintain permanent contact with underside of subfloor decking. Air barrier is installed at any exposed edge of floor. 
Crawl space walls  Insulation is permanently attached to walls. Exposed earth in unvented crawl spaces is covered with Class I vapor retarder with overlapping joints taped. 
Shafts, penetrations  Duct shafts, utility penetrations, knee walls and flue shafts opening to exterior or unconditioned space are sealed. 
Narrow cavities  Batts in narrow cavities are cut to fit, or narrow cavities are filled by sprayed/blown insulation. 
Garage separation  Air sealing is provided between the garage and conditioned spaces. 
Recessed lighting  Recessed luminaries are airtight, IC rated and sealed to drywall. Exception: luminaries in conditioned space. 
Plumbing and wiring  Insulation is placed between outside and pipes. Batt insulation is cut to fit around wiring and plumbing, or sprayed/blown insulation extends behind piping and wiring. 
Shower/tub on exterior wall  Showers and tubs on exterior walls have insulation and an air barrier separating them from the exterior wall. 
Electrical/phone box on exterior wall  Air barrier extends behind boxes or air sealed type boxes are installed. 
Common wall  Air barrier is installed in common wall between dwelling units. 
HVAC register boots  HVAC register boots that penetrate building envelope are sealed to subfloor or drywall. 
Fireplace  Fireplace walls include an air barrier. 
N1102.4.2.1 Testing option. Tested air leakage is less than 7 air changes per hour (ACH) when tested with a blower door at a pressure of 0.007 psi (50 pascals). Testing shall occur after rough in and after installation of penetrations of the building envelope, including penetrations for utilities, plumbing, electrical, ventilation and combustion appliances. During testing:
1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed;
2. Dampers shall be closed, but not sealed, including exhaust, intake, makeup air, back draft, and flue dampers;
3. Interior doors shall be open;
4. Exterior openings for continuous ventilation systems and heat recovery ventilators shall be closed and sealed;
5. Heating and cooling system(s) shall be turned off;
6. HVAC ducts shall not be sealed; and
7. Supply and return registers shall not be sealed.
N1102.4.2.2 Visual inspection option. The items listed in Table N1102.4.2, applicable to the method of construction, are field verified. Where required by local ordinance, an approved party independent from the installer of the insulation, shall inspect the air barrier and insulation.
N1102.4.3 Fireplaces. New wood-burning fireplaces shall have gasketed doors and outdoor combustion air.
N1102.4.4 Fenestration air leakage. Windows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cubic foot per minute per square foot [1.5(L/s)/m2], and swinging doors no more than 0.5 cubic foot per minute per square foot [2.5(L/s)/m2], when tested according to NFRC 400 or AAMA/WDMA/CSA101/I.S.2/A440 by an accredited, independent laboratory, and listed and labeled by the manufacturer.
Exception: Site-built windows, skylights and doors.
N1102.4.5 Recessed lighting. Recessed luminaries installed in the building thermal envelope shall be sealed to limit air leakage between conditioned and unconditioned spaces. All recessed luminaries shall be IC-rated and labeled as meeting ASTM E 283 when tested at 1.57 psi (75 Pa) pressure differential with no more than 2.0 cfm (0.944 L/s) of air movement from the conditioned space to the ceiling cavity. All recessed luminaries shall be sealed with a gasket or caulk between the housing and the interior of the wall or ceiling covering.
N1102.5 Maximum fenestration U-factor. The area-weighted average maximum fenestration U-factor permitted using trade-offs from Section N1102.1.3 shall be 0.48 in zones 4 and 5 for vertical fenestration and 0.75 in zones 4 and 5 for skylights.
SECTION N1103; SYSTEMS
N1103.1 Controls. At least one thermostat shall be installed for each separate heating and cooling system.
N1103.1.1 Programmable thermostat. Where the primary heating system is a forced air furnace, at least one thermostat per dwelling unit shall be capable of controlling the heating and cooling system on a daily schedule to maintain different temperature set points at different times of the day. This thermostat shall include the capability to set back or temporarily operate the system to maintain zone temperatures down to 55°F (13°C) or up to 85°F (29°C). The thermostat shall initially be programmed with a heating temperature set point no higher than 70°F (21°C) and a cooling temperature set point no lower than 78°F (26°C).
N1103.1.2 Heat pump supplementary heat. Heat pumps having supplementary electric-resistance heat shall have controls that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load.
N1103.2 Ducts.
N1103.2.1 Insulation. Supply ducts in attics shall be insulated to a minimum of R-8. All other ducts shall be insulated to a minimum of R-6.
Exception: Ducts or portions thereof located completely inside the building thermal envelope.
N1103.2.2 Sealing. Ducts, air handlers, filter boxes and building cavities used as ducts shall be sealed. Joints and seams shall comply with Section M1601.3.1 of this code. Duct tightness shall be verified by either of the following:
1. Post-construction test: Leakage to outdoors shall be less than or equal to eight (8) cfm (3.78 L/s) per one hundred (100) ft2 (9.29 m2) of conditioned floor area or a total leakage less than or equal to twelve (12) cfm (5.66 L/s) per one hundred (100) ft2 (9.29 m2) of conditioned floor area when tested at a pressure differential of 0.1 inch w.g. (25 Pa) across the entire system, including the manufacturer's air handler end closure. All register boots shall be taped or otherwise sealed during the test.
2. Rough-in test: Total leakage shall be less than or equal to six (6) cfm (2.83 L/s) per one hundred (100) ft2 (9.29 m2) of conditioned floor area when tested at a pressure differential of 0.1 inch w.g. (25 Pa) across the roughed in system, including the manufacturer's air handler enclosure. All register boots shall be taped or otherwise sealed during the test. If the air handler is not installed at the time of the test, total leakage shall be less than or equal to four (4) cfm (1.89 L/s) per  one  hundred  (100) ft2 (9.29 m2) of conditioned floor area.
Exception: Duct tightness test is not required if the air handler and all ducts are located within conditioned space.
N1103.2.3 Building cavities. Building framing cavities shall not be used as supply ducts.
N1103.3 Mechanical system piping insulation. Mechanical system piping capable of carrying fluids above 105°F (40°C) or below 55°F (13°C) shall be insulated to a minimum of R-3.
N1103.4 Circulating hot water systems. All circulating service hot water piping shall be insulated to at least R-2. Circulating hot water systems shall include an automatic or readily accessible manual switch that can turn off the hot water circulating pump when the system is not in use.
N1103.5 Mechanical ventilation. Outdoor air intakes and exhausts shall have automatic or gravity dampers that close when the ventilation system is not operating.
N1103.6 Equipment sizing. Heating and cooling equipment shall be sized as specified in Section M1401.3 of this code.
N1103.7 Snow-melt system controls. Snow- and ice-melting systems, supplied through energy service to the building, shall include automatic controls capable of shutting off the system when the pavement temperature is above 50°F (10°C) and no precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40° F (4°C).
N1103.8 Pools. Pools shall be provided with energy conserving measures in accordance with Sections N1103.8.1 through N1103.8.3.
N1103.8.1 Pool heaters. All pool heaters shall be equipped with a readily accessible on-off switch to allow shutting off the heater without adjusting the thermostat setting. Pool heaters fired by natural gas or LPG shall not have continuously burning pilot lights.
N1103.8.2 Time switches. Time switches that can automatically turn off and on heaters and pumps according to a pre-set schedule shall be installed on swimming pool heaters and pumps.
Exceptions:
1. Where public health standards require 24-hour pump operation.
2. Where pumps are required to operate solar-and-waste-heat-recovery pool heating systems.
N1103.8.3 Pool covers. Heated pools shall be equipped with a vapor retardant pool cover on or at the water surface. Pools heated to more than 90° F (32°C) shall have a pool cover with a minimum insulation value of R-12.
Exception: Pools deriving over sixty (60) percent of the energy for heating from site-recovered energy or solar energy source.
SECTION N1104; LIGHTING SYSTEMS
N1104.1 Lighting equipment. A minimum of fifty (50) percent of the lamps in permanently installed lighting fixtures shall be high-efficacy lamps.
SECTION N1105; REFERENCED STANDARDS
N1105.1 For purposes of this chapter, the following referenced standards, as amended, are applicable:
(a) AAMA/WDMA/CSA 101/I.S.2/A440-08; American Architectural Manufacturers Association, 1827 Walden Office Square, 550, Schaumburg, IL 60173.
(b) ASTM E 283-04; ASTM International, 100 Barr Harbor Drive, West Conshohocken, PA 19428.
(c) NFRC 100-2004; National Fenestration Rating Council, Inc., 8484 Georgia Avenue, Suite 320, Silver Spring, MD 20910. The edition of the documents listed in Chapter 6 for which no edition date is shown shall be the edition which was in effect on March 15, 2011.
(d) NFRC 400-2004; National Fenestration Rating Council, Inc., 8484 Georgia Avenue, Suite 320, Silver Spring, MD 20910. The edition of the documents listed in Chapter 6 for which no edition date is shown shall be the edition which was in effect on March 15, 2011.
(Fire Prevention and Building Safety Commission; 675 IAC 14-4.3-139.1)


SECTION 2. 675 IAC 14-4.3-139 IS REPEALED.


Posted: 08/03/2011 by Legislative Services Agency

DIN: 20110803-IR-675110084PRA
Composed: Apr 19,2024 4:43:15AM EDT
A PDF version of this document.